Megalam Cleanroom Panel HEPA/ULPA Filter
Camfil logo
Supplier
Camfil
HVAC & Climate Systems

Megalam Cleanroom Panel HEPA/ULPA Filter

Mini-pleat HEPA/ULPA ceiling panel filter for cleanroom modules, rated from 95% to 99.99995% efficiency at MPPS.

Specs verified against manufacturer documentation
Pack depth options
53, 70, 100 mm
Frame (ES variant)
Heavy-duty anodized aluminium
Pricing
Request a quote for current pricing, lead time and delivery to your airport.

The Megalam is a mini-pleat, box-type panel filter designed for direct installation into cleanroom ceiling modules, terminal housing diffusers, and standard filter housings. Microfine glass media is pleated around thermoplastic resin separators — eliminating the aluminium or paper corrugated separators of legacy deep-pleat designs — resulting in uniform airflow distribution across the full face area and a compact pack depth suited to low-ceiling cleanroom plenums.

Efficiency spans the full HEPA-to-ULPA range: from 95% at 0.3 µm up to 99.99995% at the most penetrating particle size (MPPS), making a single product family applicable to ISO Class 5 through ISO Class 1 environments depending on the grade selected. Pack depths of 53 mm, 70 mm, and 100 mm accommodate different ceiling module standards. The Megalam ES variant upgrades to heavy-duty anodized aluminium framing for longer structural life, improved resistance to oil-aerosol loading (relevant in engine test cells and MRO hangars), and bar-coded labels that embed individual factory-scan test results for installation traceability.

In aviation MRO facilities, avionics assembly areas, and precision parts manufacturing, cleanroom air quality directly influences product quality and regulatory compliance. The Megalam's compatibility with knife-edge, gel-channel, and gasket seal types means it retrofits into most existing cleanroom ceiling grids without frame replacement. For GCC operators running pressurised cleanrooms in hot ambient conditions, the all-synthetic construction avoids hygroscopic degradation issues that affect traditional glass-separator filters in high-humidity cooling transitions.

From the manufacturer’s documentation

Technical specifications.

Efficiency95% to 99.99995% at MPPS (HEPA to ULPA)
Pack depth options53, 70, 100 mm
Seal typesGasket, knife-edge, gel channel
MediaMicrofine glass, mini-pleat with thermoplastic resin separators
Frame (ES variant)Heavy-duty anodized aluminium
Traceability (ES)Individual bar-coded scan test results per filter
Best for

Use cases.

  • Cleanroom ceiling modules in avionics assembly and aircraft component manufacturing
  • MRO facility precision parts areas and paint mixing rooms
  • ISO Class 5–8 controlled environments in aerospace test facilities
  • Terminal housing diffusers in pharmaceutical and laboratory applications
  • Retrofit replacement into existing cleanroom ceiling grids across multiple seal standards
Megalam Cleanroom Panel HEPA/ULPA Filter by Camfil · Aviation Souk