ACMR Air-Cooled Scroll Chiller
SKM Air Conditioning logo
Supplier
SKM Air Conditioning
HVAC & Climate Systems

ACMR Air-Cooled Scroll Chiller

Compact R-410A scroll chiller from 8 to 279 TR — the modular, low-vibration choice for smaller buildings and distributed plant configurations.

Specs verified against manufacturer documentation
Cooling capacity range
8–279 TR
Cooling capacity range (kW)
28–981 kW
Refrigerant
R-410A
EER at 95 °F ambient (typical)
~9.9–10.8 Btu/W·h
Pricing
Request a quote for current pricing, lead time and delivery to your airport.

The ACMR is SKM's air-cooled scroll chiller range, using hermetic scroll compressors on R-410A refrigerant to cover 8 to 279 TR (28–981 kW) across 56 models on 50 Hz and 60 Hz. Scroll compressors have approximately 70% fewer moving parts than reciprocating equivalents, translating to quieter operation, lower vibration, and reduced maintenance. Small-capacity models up to 45 TR use brazed-plate heat exchangers (stainless-steel construction, rated to 421 psig on the water side); larger models switch to direct-expansion shell-and-tube evaporators, maintaining compatibility with standard chilled-water distribution systems at higher flow rates.

Performance data from the selection guide shows EER values consistently in the 9.9–10.8 Btu/W·h range at 95 °F (35 °C) ambient, with usable capacity maintained through 118.4 °F (48 °C) ambient. Models with larger capacity use electronic expansion valves; smaller units use thermostatic valves. The galvanised steel casing is phosphatised and powder-coated to pass a 1,000-hour 5% salt-spray test (ASTM B117), directly relevant to the saline-air environments of Gulf coastline and port-adjacent facilities. Certified under AHRI 550/590 and 551/591.

The ACMR is specified for medium-scale commercial buildings — office blocks, shopping centres, clinics, schools, and villa compounds — where the load does not justify a screw chiller but a packaged DX system is insufficient. Multiple units can be deployed in parallel for larger loads with inherent N+1 redundancy; losing one compressor degrades rather than eliminates cooling capacity, a useful operational resilience property for airport concessions buildings, cargo terminals, and similar facilities where total loss of cooling is operationally disruptive.

From the manufacturer’s documentation

Technical specifications.

Performance & capability
Cooling capacity range8–279 TR
Cooling capacity range (kW)28–981 kW
RefrigerantR-410A
Compressor typeHermetic scroll (single or multiple per unit)
Evaporator type (small units ≤45 TR)Brazed-plate heat exchanger (BPHE), stainless steel
Evaporator type (larger units)Direct-expansion shell-and-tube
EER at 95 °F ambient (typical)~9.9–10.8 Btu/W·h
Ambient operating range0 °C to +52 °C
CertificationsAHRI 550/590 & 551/591; ISO 9001; ISO 14001; OHSAS 18001
Power & environment
Power supply (standard 50 Hz)380–415 V / 3 Ph / 50 Hz
Best for

Use cases.

  • Office buildings, clinics, and schools requiring a compact, low-vibration chilled-water system
  • Airport concessions buildings, cargo terminals, and small landside facilities
  • Shopping centres and retail parks where multiple units provide capacity flexibility
  • Coastal and port-adjacent sites benefiting from the ASTM B117 salt-spray-rated casing
  • Parallel multi-unit configurations delivering N+1 cooling redundancy without screw chiller first cost
ACMR Air-Cooled Scroll Chiller by SKM Air Conditioning · Aviation Souk