APCY-H High-Efficiency Air-Cooled Screw Chiller
High-efficiency 81–519 TR air-cooled screw chiller with heavy-duty copper-tube condenser, available in both 50 Hz and 60 Hz configurations.
The APCY-H is the widest-capacity model in SKM's APCY air-cooled screw range, spanning 81 to 519 TR (285–1,825 kW) and covering both 50 Hz and 60 Hz power supplies — the broadest market reach in the lineup. Its condenser coil is built from seamless Hi-X copper tubes mechanically bonded to aluminium fins, a configuration that offers long-term robustness in harsh outdoor environments and higher resistance to mechanical damage than MCHE alternatives during maintenance.
Performance data from the Quick Selection Guide (50 Hz, 95 °F ambient) shows EER values consistently in the 10.9–11.6 Btu/W·h band across the mid-capacity models, with rated capacity retention down to 118.4 °F (48 °C) ambient — a direct measure of hot-climate capability. The semi-hermetic screw compressor with stepless modulation keeps part-load operation efficient across the Gulf's long transition seasons. The unit ships factory-assembled, pre-charged with R-134a, and is rated AHRI 550/590 and 551/591 certified.
The APCY-H targets large central plants and campus-scale chilled-water systems where the combination of high capacity, dual-frequency availability, and copper-tube condenser durability matters more than absolute weight minimisation. Airports, hospitals, universities, large-scale mixed-use developments, and Gulf-region industrial campuses operating 60 Hz networks are typical end users. The 60 Hz variant also makes this series exportable across the Americas and parts of Asia without specification re-engineering.
Technical specifications.
| Cooling capacity range | 81–519 TR |
| Cooling capacity range (kW) | 285–1,825 kW |
| Refrigerant | R-134a |
| Compressor type | Semi-hermetic screw, stepless capacity control |
| Condenser coil | Seamless Hi-X copper tube / aluminium fin (heavy-duty) |
| EER at 95 °F ambient (typical mid-range) | ~11.0–11.6 Btu/W·h |
| Ambient operating range | −4 °C to +52 °C |
| Power supply | 380–415 V / 3 Ph / 50 Hz or 380–400 V / 3 Ph / 60 Hz |
| Certifications | AHRI 550/590 & 551/591; ISO 9001:2015; ISO 14001:2015; ISO 45001:2018 |
Use cases.
- ›Large airport terminal and concourse central plant up to 519 TR per unit
- ›Hospital and healthcare campus central chilled-water systems
- ›University and government-complex HVAC requiring AHRI-certified, dual-frequency equipment
- ›Industrial campuses on 60 Hz networks in the Gulf and export markets
- ›High-availability plant configurations demanding copper-tube condenser durability